Smart Cooling Tower for Data Centres
The computers in a data centre run day and night and give off a lot of heat. That heat needs to be removed to keep the computers running reliably. Planet Transformation’s cooling tower is designed to do this using less electricity.
The tower works like a chimney. Outside air enters at the bottom and picks up heat from the data centre. As the air warms, it rises naturally and flows out at the top, drawing more cool air in at the bottom.
On warmer days, or when the computers give off more heat, fans can provide extra airflow. The idea is to use sensor readings and weather forecasts to predict when extra cooling will be needed.
Computer simulations by Sirris showed that air flowed naturally through the tower. How much heat the full system can remove and how much electricity it can save still need to be tested in practice.
Lorem ipsum dolor sit amet, consectetur adipiscing elit. Ut elit tellus, luctus nec ullamcorper mattis, pulvinar dapibus leo.
The engineering behind the cooling tower
Why data centres need more efficient cooling
Almost all the electricity used by servers ends up as heat. A data centre with a continuous 3 megawatt (MW) IT load therefore produces roughly 3 MW of heat, or around 26 gigawatt-hours (GWh) of heat over a year. The cooling system has to remove that heat around the clock, including during hot weather and periods of high computing demand.
the challenge
This challenge is growing as AI and high-performance computing increase the amount of computing power installed in individual server racks. The International Energy Agency estimates that data centres worldwide used around 415 terawatt-hours (TWh) of electricity in 2024, about 1.5% of global electricity consumption. In its base case, the IEA projects this will rise to around 945 TWh by 2030. These figures cover total data centre electricity use, including IT equipment, cooling and other infrastructure. IEA
the project
The Planet Transformation project focuses on the electricity needed to remove heat. Its aim is to use the airflow created by the heat itself whenever conditions allow, with fans and additional cooling available when needed.
How the tower transfers heat to outside air
In the proposed design, heat from the servers is carried to the tower by a liquid cooling circuit. Inside the tower, a heat exchanger passes that heat to outside air flowing through a vertical gap between the inner and outer walls. Fins increase the surface area over which heat can transfer to the air.
As the air warms, it becomes less dense and rises. This creates a small pressure difference that draws fresh air in at the bottom and pushes warmer air out at the top. This is known as the stack effect. One of the tower configurations studied was approximately 32 metres high.
the engineering challenge
The engineering challenge is to make the most of that small pressure difference. The heat exchanger needs enough surface area to transfer heat effectively, while the inlets, fins, ducts and outlets must let air pass with as little resistance as possible. A heat exchanger that transfers heat well but restricts airflow could reduce the benefit of natural draft. The tower and heat exchanger therefore have to be designed together.
the concept
The concept combines three operating modes.
Operating mode How it works
Natural draft The heat in the tower drives airflow. A bypass is intended to give air a low-resistance path past the fan assemblies when they are idle.
Fan-assisted cooling Variable-speed fans increase airflow when natural draft alone provides insufficient cooling.
Additional cooling A separate cooling system can support the tower when outdoor conditions or operating limits make it necessary. Its capacity would be determined for each installation.
What Sirris investigated
Sirris used computational fluid dynamics (CFD) to study how air moves through the tower and where temperatures rise. CFD uses a computer model to calculate airflow, pressure and temperature in a defined geometry. It allows engineers to compare design options before building a physical installation.
The simulation programme examined different outdoor temperatures, including 0°C, 20°C and 35°C, and compared configurations with and without fan assistance. Natural draft developed in the passive scenarios studied. In the hotter scenarios, the model showed lower air mass flow, making hot-weather operation an important part of the design work.
In a later study, Sirris compared the open and closed bypass positions while the fan was running. Under the modelled conditions, closing the bypass increased the outgoing airflow. With the bypass open, some of the warm air leaving the fan circulated back towards its inlet. That matters because air moving through a fan only helps cool the installation if it carries heat out of the tower. The result gives the engineering team a clear design task: keep the air path open for natural draft when fans are idle and limit recirculation when they are running.
The CFD work focused on the air side of the system. Heat was applied to a surface in the model. A complete liquid cooling circuit, with its pumps, pipework, heat exchangers and server operating temperatures, still needs to be assessed as part of an integrated system. The simulations show how the tower responds to an imposed heat load. The next stage is to establish how much heat a complete installation can remove while keeping the coolant within the temperature range the servers require.
Why the coolant temperature matters
The tower’s ability to cool depends on the temperature difference between the liquid and the outside air. Consider a liquid cooling circuit designed to supply coolant to the servers at 35°C and receive it back at 45°C. With outside air at 20°C, there is room for a dry heat exchanger to cool the returning liquid towards the supply temperature. At 35°C outside, the air is already at the target coolant supply temperature. A dry heat exchanger requires a temperature difference to transfer heat, so more airflow alone cannot achieve a 35°C supply in those conditions.
That example illustrates why a practical installation needs to be designed around the specific servers, the local climate and the temperatures the cooling circuit can accept. A higher allowable coolant temperature can widen the range in which the tower can operate on its own. A lower target can increase the need for additional cooling during warm periods.
Predictive control and the next stage
The proposed control system would combine live measurements, such as coolant temperature and airflow, with the expected IT load and the weather forecast. If a hot afternoon is forecast, the controller could prepare for the change and adjust fan speed as the available cooling margin narrows. As conditions improve, it could reduce fan speed and return to natural draft when the measured temperatures allow it.
The next engineering step is to model and test the tower together with the liquid circuit, then compare it with a reference cooling system serving the same IT load at the same coolant temperatures. Over a full year of local weather conditions, that comparison would show how many hours the tower can run on natural draft, how often it needs fans or additional cooling, and how much electricity the complete cooling system uses, including pumps and fans.
The goal is to make natural draft do a measurable share of the cooling work throughout the year while maintaining the cooling conditions that a data centre needs to operate reliably.